The Most Common Problems with the Sakura TEC Embedding Center (and How to Fix Them)

Warning sign for Sakura TEC 5 Embedding Center issues and solutions.

By Tyler Harper

The Sakura TEC 5 Embedding Center is a trusted piece of histology lab equipment used to embed tissue specimens in paraffin before sectioning. Like any lab instrument, it requires proper care and maintenance to perform reliably day after day. When things go wrong, however, a few issues tend to appear more often than others.

To help labs troubleshoot quickly, we spoke with Daniel Silva, a biomedical equipment technician, about the most common problems he sees with the Sakura TEC 5—and how to fix them.


1. The Cold Plate Stops Cooling

Symptom:
The cold plate no longer cools or doesn’t reach the expected low temperature.

Most Likely Causes:

  • Failed cooling fan: A small fan on the back of the unit moves air across the thermoelectric (Peltier) cooler. When that fan fails, there’s no airflow, and the plate can’t dissipate heat.
  • Leak or blockage in paraffin lines: Paraffin leaks can interfere with airflow or heat transfer inside the system.

Fix:
Check the fan first—if it’s not spinning, replace it. The TEC 5 uses a Peltier cooling system rather than a refrigerant (no Freon), so airflow is critical. If the fan is functional, inspect the paraffin lines for leaks or buildup that could be disrupting cooling.


2. Line 1 Won’t Heat or Dispense Paraffin

Symptom:
Everything else heats properly, but Line 1 stays cold and will not dispense paraffin.

Most Likely Cause:
A failed heating element in Line 1. Each paraffin line has its own dedicated heating element, and Line 1 is statistically the one that fails most often.

Fix:
Replace the heating element for that specific line. Because each line is independently wired, one can fail without affecting the others. A technician should verify voltage and continuity before replacement to confirm the fault.


3. The Valve Is Stuck or Clogged (No Dispensing or Continuous Flow)

Symptom:

  • The system heats normally, but nothing dispenses.
  • Or, the valve opens and won’t close, allowing paraffin to flow uncontrollably.

Most Likely Causes:

  • Dirty or reused paraffin: Recycled wax can carry debris that clogs or gums up the valve.
  • Contaminated paraffin buildup: Over time, unfiltered paraffin can solidify inside the valve mechanism.
  • Mechanical valve failure: Less common, but possible after heavy use.

Fix:
Always use clean, fresh paraffin—never re-melt used wax. If clogging has already occurred, a technician will need to flush the lines and clean or replace the valve. This is not a user-serviceable task, as it requires specialized tools and heating procedures.


4. One Side of the Workstation Isn’t Heating

Symptom:
Either the left or right working area remains cold while the opposite side heats correctly.

Most Likely Causes:

  • A blown fuse for that side’s heating circuit.
  • A failed heating mat or element under the work surface.

Fix:
Each side of the TEC 5 has its own fuse and heating element. Check the fuse first—it’s located inline with the heating circuit. If the fuse is intact, the heating element itself may have failed and should be replaced. Both sides use the same design, so failure can occur on either side equally.


Preventive Tips for the Sakura TEC 5

  • Use only clean, laboratory-grade paraffin. Avoid reusing wax that’s been exposed to debris or tissue.
  • Keep airflow clear. Dust and wax buildup around the rear cooling fan can quickly cause overheating and cold-plate failure.
  • Schedule routine maintenance. Have a biomedical technician inspect fuses, fans, and heating elements annually.
  • Flush lines when contamination is suspected. Early cleaning prevents clogs that can lead to more costly valve replacements.

Final Thoughts

The Sakura TEC 5 Embedding Center is generally dependable, but like any high-use histology instrument, it benefits from consistent maintenance and a clean workflow. Most issues—from failed fans to clogged valves—can be prevented with regular inspection and proper paraffin handling. Keeping these basics in mind will minimize downtime and keep your lab running smoothly.


Frequently Asked Questions (FAQ)

1. What does the Sakura TEC 5 Embedding Center do?

The Sakura TEC 5 is a paraffin embedding system used in histology and pathology labs. It allows technicians to embed biological tissue samples in paraffin wax before microtomy, ensuring stable sections for microscopic analysis.

2. Why is my Sakura TEC 5 cold plate not cooling?

If the cold plate stops cooling, it’s most often due to a failed rear cooling fan or a paraffin leak that interferes with airflow. The Sakura TEC 5 uses a Peltier (thermoelectric) cooling system, so airflow is essential. Replacing the fan or fixing leaks usually resolves the issue.

3. What should I do if one of the paraffin lines isn’t dispensing?

If one of the lines—especially Line 1—doesn’t heat or dispense, the heating element for that line has likely failed. Each line has its own heating circuit, so replacing that individual element typically restores function.

4. How do I prevent clogging in the paraffin lines?

Avoid reusing paraffin, as it can introduce contaminants and debris that solidify inside the valve. Always use clean, fresh paraffin and schedule periodic professional maintenance to keep lines clear.

5. Can users flush the lines themselves?

No. Flushing paraffin lines requires specific tools and heat-control procedures. It should be performed by a qualified biomedical technician to avoid damage to the system or safety risks.

6. What maintenance should I perform regularly?

  • Wipe away excess wax daily.
  • Keep the rear fan area dust-free.
  • Use only clean paraffin.
  • Have a technician inspect fuses, fans, and heating elements annually.

Regular care prevents most of the common TEC 5 issues before they start.


Professional Service & Support for Sakura TEC 5 Embedding Centers

Even with the best care, equipment like the Sakura TEC 5 Embedding Center sometimes needs professional attention. That’s where our team comes in.

At Amtech Medical, we don’t just provide histology and dermatology equipment—we also offer diagnostic and repair services for embedding centers, cryostats, and other lab instruments. Whether your TEC 5 needs a fan replacement, heating element repair, or a full system inspection, our technicians can help you get back up and running quickly.

Our service options include:

  • On-site or depot repair for embedding centers
  • Preventive maintenance programs for lab equipment
  • Replacement parts for Sakura, Leica, and Thermo Fisher systems
  • Technical support and troubleshooting

We specialize in fast turnaround times and cost-effective repairs—so your lab can focus on what matters most: patient care and accuracy.

👉 Need help with your Sakura TEC 5?
Contact our service department or email info@amtechmedical.com to schedule a repair or request a quote.


Additional Resources


Tek 5 Brochure

Tek 5 Key Features


The Most Common Problems with Midmark Procedure Lights (And How to Fix Them)

Surgical light and medical equipment from Amtech Medical.

Midmark procedure lights are a staple in medical offices, dermatology practices, and surgical suites. They’re designed to provide bright, reliable illumination, whether mounted on rolling stands for portability or ceiling-mounted for fixed, overhead lighting.

Midmark’s lineup has evolved over time, with two main models commonly seen today:

  • Midmark 355 – the older, halogen-bulb style light.
  • Midmark 255 – the newer LED-based system.

Both are well-built and long-lasting, but like any piece of equipment, they have their quirks. Below are the most common problems technicians see with Midmark lights — and what you can do about them.


1. Midmark 355 – Light Won’t Turn On

The most common issue with the older Midmark 355 is simple: the light won’t come on.

What it looks like:

  • Power switch is on, but the bulb doesn’t light up.
  • Sometimes the bulb works for a while, then fails again within a short timeframe.

Why it happens:

  • Most often, the halogen bulb has burned out.
  • Repeatedly blowing bulbs may indicate the wrong bulb type was used or an issue with the transformer providing too much voltage.
  • In some cases, wiring can get pinched inside the mounting tube if the light wasn’t installed correctly.

Fix:

  • Replace the bulb. Always use gloves — oils from bare fingers can cause halogen bulbs to overheat and crack.
  • If bulbs are failing quickly, check transformer settings. Lowering the voltage slightly can extend bulb life.
  • If the light cuts out only in certain positions, the wiring may be pinched and will need to be re-routed by a technician.

2. Midmark 255 – LED Board Failure

The Midmark 255 uses an LED board instead of a halogen bulb. LEDs last much longer, which means fewer service calls — but when they fail, it’s usually the entire board.

What it looks like:

  • Light stops working entirely.
  • No response from the unit even though power is connected.

Why it happens:

  • The most common cause is a failed LED board.
  • Power surges or electrical fluctuations can shorten the lifespan of the board.

Fix:

  • Replacing the LED board is the standard solution.
  • Using surge protection can help reduce the risk of failure from sudden electrical spikes.

3. Overheating or Cracked Bulbs in the 355

Occasionally, users report that a bulb cracks almost immediately after installation.

Why it happens:

  • This usually occurs when the bulb was installed without gloves. Oils from skin transfer onto the glass, and once the bulb heats up, the spot overheats and causes the glass to crack.

Fix:

  • Always use gloves or a lint-free cloth when handling halogen bulbs.
  • Ensure the light is powered off during replacement — halogens heat up almost instantly and can cause burns.

4. Wiring Issues During Installation

While not as common, wiring problems can create intermittent power failures.

What it looks like:

  • Light works only in certain positions.
  • Power cuts off when the arm is moved.

Why it happens:

  • If the wiring inside the tubing wasn’t routed properly during installation, it can get pinched or strained. Over time, this leads to power interruptions.

Fix:

  • A technician will need to remove and re-feed the wiring correctly through the arm assembly. Once corrected, the problem typically does not return.

5. Lights That Sway or Won’t Hold Position

Another issue that occasionally shows up is the light swaying or drifting out of place when you try to position it. This is especially frustrating during a procedure, when steady illumination is critical.

What it looks like:

  • The light won’t stay in place after being positioned.
  • It drifts slowly, or feels “loose” at the pivot point.

Why it happens:

  • This usually means the counterweight system isn’t balanced correctly. Over time, or after adjustments, the counterweight can shift out of alignment, making it impossible for the light to hold its position.

Fix:

  • In some cases, you can re-level the light by adjusting the counterweight position.
  • If the counterweight itself is worn or damaged, it may need replacement to restore proper balance.

The Bigger Picture

Midmark procedure lights are generally very reliable. The 355 halogen model has the most common issues simply because bulbs wear out faster than LEDs. The 255 LED model requires far fewer service calls, though replacing the board is more involved than swapping a bulb.

Other occasional issues — from wiring to counterweights — typically stem from installation or long-term wear. The good news? All are repairable, and once fixed, Midmark lights continue to provide years of dependable service.


Preventive Tips for Midmark Lights

  • Use gloves when handling halogen bulbs to avoid cracking from skin oils.
  • Install surge protection to safeguard against power surges that can damage LEDs.
  • Have lights professionally installed to prevent pinched wiring.
  • Check counterweight balance if lights start swaying or drifting.
  • Keep spare bulbs on hand for the Midmark 355.
  • Schedule routine maintenance to check voltage settings, wiring, and light output.

Final Thoughts

Midmark procedure lights are simple, durable, and effective. For most users, problems are rare and easily solved — usually a bulb swap for the 355, an LED board replacement for the 255, or a quick adjustment to balance the counterweight.

By following basic preventive care and addressing issues early, you can maximize uptime and extend the life of your lights. And when the fix requires more than a bulb or board swap, Amtech Medical’s service team is here to help with expert troubleshooting, repairs, and replacement parts.

The Most Common Problems with the Candela Vbeam Perfecta (And How to Fix Them)

High-tech medical aesthetic device for skin rejuvenation and anti-aging treatments.

The Candela Vbeam Perfecta is one of the most trusted pulsed dye lasers in dermatology. Designed primarily for vascular treatments such as veins, rosacea, and scars, it also has off-label uses for warts and other skin conditions.

What makes the Vbeam unique is its 595 nm wavelength. Sitting in the yellow-orange range of visible light, this wavelength is absorbed especially well by blue vessels, making it highly effective for vascular work. Unlike solid-state lasers, the Vbeam is a dye-based laser — and that brings its own quirks, especially around routine maintenance and long-term reliability.

Here are the most common problems (and error codes) we see with the Vbeam Perfecta, what they mean in real-world use, and how to address them.


1. Fault 15 – Transmission Error

If you’ve ever seen your Vbeam throw a “Fault 15” message mid-calibration, you know how frustrating it is. Treatments grind to a halt, staff get flustered, and patients are left waiting.

What’s happening here is a loss of transmission between the laser head and the fiber. In plain terms, the light leaving the machine isn’t matching what’s reaching the handpiece. Once the system detects more than ~25–30% loss, it throws the error and shuts things down.

What it looks like in practice:

  • The unit won’t complete calibration.
  • Output feels weak or inconsistent.
  • Staff notice “dead spots” when firing at the skin.

Why it happens:
There are three main culprits:

  1. A damaged fiber line.
  2. Lenses in the handpiece slider that have worn down or gotten dirty.
  3. A debris shield that’s overdue for cleaning or replacement.

Fix and best practices:
Daily cleaning of the debris shield with alcohol is the easiest way to prevent this fault. If the error persists, try swapping sliders. For example, if you were using the 7 mm slider and Fault 15 appears, switch to the 5 mm or 10 mm slider. If the error clears, the issue is with the slider lens, which can be repaired or replaced. If it persists across sliders, the fiber itself may be compromised — that’s when you’ll need a technician.


2. Fault 6 – Calibration Fault

Calibration is one of the built-in safety nets of the Vbeam, and it’s where many problems get caught. Every time you adjust the energy, the unit runs a self-check to make sure it can deliver what you’re asking for. But if the system can’t hit those numbers, it throws a Fault 6 calibration error.

What users notice:

  • The error usually appears during calibration rather than mid-treatment.
  • The system fails to meet the requested output energy.
  • No amount of slider swapping or debris shield cleaning fixes it.

What’s going on inside:
Unlike Fault 15, which is usually a transmission issue, Fault 6 points to an internal generation problem. That means the laser head itself isn’t producing enough energy. It could be a dye cartridge nearing end-of-life, worn mirrors, or inefficiencies inside the optics and reflectors.

Solution:
This is not a user-fixable issue. If Fault 6 appears repeatedly, it’s time to call for service. A technician will need to evaluate whether it’s the dye, optics, or another component inside the head.


3. Fault 12 – Energy Out of Range / Energy Imbalance

If you’ve ever had the machine throw an “Energy Out of Range” or imbalance error, you were probably dealing with the early signs of dye depletion.

How it shows up in the clinic:

  • Energy output starts to feel inconsistent, even when settings haven’t changed.
  • Treatments may seem weaker than normal.
  • The machine eventually displays Fault 12 or a related imbalance warning.

Why it happens:
The Vbeam generates a series of sub-pulses that need to fire in sequence at balanced energy levels. If the dye is breaking down, those pulses lose their balance. The system recognizes this and flags the error before performance degrades further.

Fix:
This one almost always means it’s time for a dye kit replacement. It’s not something a user can handle on their own, but once the kit is replaced and the system recalibrated, output consistency returns.


The Bigger Picture

The Vbeam Perfecta is one of the most reliable and widely used dermatology lasers in the world, but it comes with one unavoidable fact: the dye has a limited lifespan.

On average, dye kits last around 40,000–50,000 pulses, with a guarantee of ~20,000 shots or one year (whichever comes first). A busy clinic can burn through a kit in months, while a slower-paced practice may find their kit expiring on the calendar rather than the shot count. Either way, replacement is a built-in cost of ownership.


Preventive Tips for Vbeam Users

  • Clean the debris shield daily to reduce the chance of transmission errors.
  • Replace debris shields proactively before they cause interruptions.
  • Rotate handpiece sliders if you suspect one lens is failing.
  • Track shot counts to anticipate dye replacement before performance drops.
  • Schedule annual preventive maintenance for calibration, optics, and dye checks.

Final Thoughts

The Candela Vbeam Perfecta has earned its place as one of the most versatile lasers in dermatology. Its unique 595 nm wavelength makes it unmatched for vascular treatments, and its proven results have kept it in high demand across the country.

Still, it’s important to recognize that this is a dye laser, and dye replacement is part of the ownership equation. Add in common error codes like Fault 6, 12, and 15, and you see why preventive care matters so much.

The takeaway: treat your Vbeam well, stay ahead of routine maintenance, and you’ll enjoy years of reliable performance. And when a problem goes beyond cleaning a shield or swapping a slider, that’s when Amtech Medical’s technicians step in to keep your laser running at its best.


Amtech Service

Do you need support with your equipment? Amtech Medical is here to help.

Contact page for service

The Most Common Problems with Silverfox Chairs (And How to Fix Them)

ADA recessed treatment table with advanced medical equipment for healthcare.

Silverfox chairs are a common sight in dermatology offices, medspas, and aesthetic clinics. They’re versatile, comfortable for patients, and priced well compared to other brands. But like any high-use equipment, they have weak spots that show up again and again in the field.

We sat down with our technician, Daniel Silva, to talk through the issues he sees most often. Below are the most common Silverfox chair problems, how to spot them, and what you can do about it.


1. Actuators That Stop Working

If you press the remote and nothing happens — no sound, no movement — chances are an actuator has failed.

What it looks like:

  • Backrest won’t recline or return upright
  • Footrest won’t move
  • Chair height doesn’t adjust

Daniel explained: “Most of the time, it’s the actuator itself, not the main board. You hit the button and nothing happens. No clicking, no grinding — just dead.”

👉 Fix: This is not user-serviceable. A technician will test whether the actuator or control board is at fault, but usually it’s the actuator that needs replacing.


2. Armrests That Break or Dangle

One of the weakest points on Silverfox chairs is the armrest connection. Patients often lean heavily on them when getting up, but they’re not designed to carry full body weight.

What it looks like:

  • Armrest suddenly feels loose or drops
  • Nut and bolt that act as a “stop” strip out
  • Armrest dangles and won’t stay in position

Daniel noted: “There’s a bolt that takes all the pressure. If someone pushes too hard, it strips, digs into the metal, and the armrest just hangs.”

👉 Fix: If the damage is light, a technician may be able to re-thread or replace the bolt. If badly stripped, the armrest assembly usually needs replacing.


3. Plastic Covers Coming Loose

Silverfox uses lightweight plastic panels around the base and under upholstery, held in place with push pins. Over time, these pins wear out.

What it looks like:

  • Plastic panel hanging down under the chair
  • Cosmetic gaps in the upholstery trim
  • Staff taping covers in place until service arrives

Daniel added: “It doesn’t stop the chair from working, but it looks unprofessional. Most offices just remove the panels until I can replace the pins.”

👉 Fix: If you have replacement push pins, you can reattach panels yourself. Otherwise, a technician can secure or replace the covers quickly.


4. Footrest Extension Sensor

Many Silverfox chairs have a footrest extension that slides out for taller patients. The problem? If it’s not fully pushed back in, the chair’s safety sensor disables footrest movement.

What it looks like:

  • Footrest doesn’t respond to remote
  • Other chair functions still work fine
  • Extender visibly sticking out

Daniel explained: “If the extender’s out, the sensor blocks the footrest. Push it all the way back in and it works again.”

👉 Fix: Always check the footrest extension before calling for service — this is an easy fix.


5. Worn-Out Upholstery

Over time, the upholstery on Silverfox chairs begins to show wear — especially in high-traffic practices where the same chair is used dozens of times a day.

What it looks like:

  • Cracking or peeling on the seat and backrest
  • Fading or discoloration on lighter colors
  • Small tears around high-stress seams, often near armrests or edges

In one dermatology office, patients started noticing small cracks in the seat cushion, which eventually split open. The chair still functioned fine mechanically, but cosmetically it gave the wrong impression.

👉 Fix: Upholstery wear is mostly cosmetic, but it affects the professional look of your practice. Silverfox chairs can often be reupholstered or fitted with replacement covers. If wear is extensive, some offices choose to replace the chair entirely.


The Bigger Picture

Silverfox chairs are affordable and practical, but their design does include some weak points:

  • Actuators fail without warning
  • Armrests strip easily under weight
  • Plastic panels come loose from worn pins
  • Footrest sensors lock out movement if extensions aren’t seated properly
  • Upholstery cracks and fades with heavy use

These issues don’t mean the chairs are bad — just that practices should be prepared for regular service and occasional part replacements.


Preventive Tips for Longer Chair Life

  • Remind patients not to push down heavily on the armrests.
  • Inspect gaskets, bolts, and armrests monthly for early signs of wear.
  • Keep replacement push pins on hand for loose covers.
  • Train staff to check the footrest extension sensor when functions stop working.
  • Clean and condition upholstery regularly to slow cracking and fading.
  • Schedule preventive maintenance to catch actuator wear before failure.

Final Thoughts

Silverfox chairs do their job well, but they’re not indestructible. By knowing the common issues — and spotting the symptoms early — you can minimize downtime and keep your practice running smoothly.

And when problems go beyond quick fixes, that’s when Amtech Medical’s service team is here to help with repairs, upholstery, parts replacement, and ongoing maintenance.


Amtech Service

Do you need help with your equipment? Amtech Medical is here to help.

Contact page for service

The Most Common Problems with Tabletop Autoclaves (And How to Fix Them)

Automatic medical sterilizer for hospital and clinical use.

TabTabletop autoclaves are the backbone of sterilization for small medical offices, dermatology practices, dental clinics, and medspas. Compact yet powerful, they ensure instruments are sterilized safely, protecting both patients and providers.

But like any equipment, these autoclaves develop recurring issues — usually from daily wear, skipped maintenance, or environmental factors like poor water quality. The good news is that many of these problems can be diagnosed quickly, and in some cases, fixed without waiting on a service call.

Below we’ll walk through the most common autoclave problems, what causes them, and what to do next. Along the way, we’ll include real-world scenarios to show how these issues play out in the field.


1. Autoclave Won’t Power On

Imagine this: a dermatology clinic is getting ready for back-to-back procedures, but the autoclave won’t even light up. The front desk is panicking, because without sterilized instruments, the day’s schedule is on the line.

Common Causes:

  • Loose power cable or faulty outlet
  • Tripped circuit breaker or blown fuse
  • Faulty door switch (some autoclaves won’t power unless the door is fully closed)

Fix:

  • Confirm the outlet works by testing another device.
  • Inspect the fuse or breaker and replace/reset as needed.
  • Check that the door is latched tightly — on many tabletop units, an incomplete latch interrupts the power circuit.
  • If it still won’t start, the control board or wiring likely needs professional repair.

2. Chamber Won’t Pressurize

One of the most common calls we get is: “The cycle runs, but the autoclave never builds pressure.” In one case, a medspa reported hearing faint hissing during every cycle — sure enough, the door gasket had cracked, and steam was escaping instead of building pressure.

Causes:

  • Worn or cracked door gasket
  • Loose or unevenly latched door
  • Scale buildup around valves from using tap water instead of distilled
  • Leaky fittings or solenoid valves

Fix:

  • Replace door gaskets annually, or sooner if cracks or flattening appear.
  • Confirm the door closes evenly — sometimes hinges loosen over time.
  • Clean valves and fittings.
  • Always use distilled water only to prevent scale buildup.

3. Sterilization Cycle Won’t Complete

A dental practice once reported their autoclave was aborting halfway through every cycle. After inspection, we found the drain filter was clogged with cotton fibers from gauze packs. Airflow was restricted, steam couldn’t circulate, and cycles failed.

Causes:

  • Overloaded chamber (steam can’t circulate)
  • Drain filter clogged
  • Faulty temperature or pressure sensors
  • Heating element wearing out

Fix:

  • Load instruments loosely, allowing space for steam.
  • Clean the drain filter weekly — it’s small but critical.
  • If problems persist, sensors or heaters may require replacement.

4. Wet Packs After a Cycle

Few things frustrate staff more than opening the door to find wet, dripping packs. Not only is it unsafe (moisture can harbor microbes), but it means re-running the cycle — doubling sterilization time.

Causes:

  • Chamber overloaded
  • Improper wrapping material
  • Drain line partially clogged
  • Door gasket leaking steam at the wrong time

Fix:

  • Reduce load size and leave room between packs.
  • Only use wraps designed for autoclaves.
  • Inspect drain lines and clean if blocked.
  • Replace or lubricate the door gasket if leaking.

5. Strange Noises or Leaks

Another medspa complained about “knocking” sounds during cycles. After inspection, we found scale buildup inside the steam lines — mineral deposits from using tap water. The fix was a thorough descaling and a reminder to always use distilled water.

Causes:

  • Solenoid valve beginning to fail
  • Loose or worn chamber gasket
  • Mineral buildup in chamber or tubing

Fix:

  • Replace worn seals and valves.
  • Perform regular descaling treatments (especially in hard-water areas).
  • Call for service if noises persist — they can indicate valve timing issues.

6. Error Codes or “Service Required”

Modern tabletop autoclaves have error codes for safety. These can be intimidating, but often they point directly to the issue.

For example, an error might indicate a temperature sensor failure — meaning the unit isn’t sure how hot it actually is. In one dermatology office, a persistent error code turned out to be nothing more than a faulty door switch, replaced in under 30 minutes.

Common Codes Indicate:

  • Sensor failure (temp/pressure)
  • Electrical heating fault
  • Board communication error
  • Door/lid not sealed properly

Fix:

  • Try a full power cycle.
  • Refer to the user manual for code meaning.
  • Some fixes are user-friendly (gaskets, switches), but persistent codes often need a technician.

Preventive Care to Avoid Most Problems

In almost every scenario above, the problem could have been prevented with basic care.

  • Use distilled water only — tap water = scale buildup.
  • Clean the drain filter weekly.
  • Check gaskets monthly and replace annually.
  • Avoid overloading to allow proper steam circulation.
  • Schedule yearly preventive maintenance to catch small issues before they shut you down.

Final Thoughts

Tabletop autoclaves are dependable workhorses, but they’re not invincible. From leaking gaskets to wet packs, most problems follow predictable patterns and can be solved with simple checks.

By knowing what to look for — and addressing issues early — you can keep your autoclave running smoothly, minimize downtime, and protect patient safety.

And when the fix goes beyond basic troubleshooting? That’s where professional technicians step in. Having a trusted service partner means peace of mind that your autoclave is always ready when you need it most.


Looking for a Replacement?

Sometimes, repairing an older tabletop autoclave just isn’t cost-effective. If the heating element, control board, or chamber itself is failing, the repair costs may approach the price of a new unit.

That’s where Amtech Medical’s refurbished autoclaves come in.

We stock a range of used, professionally reconditioned autoclaves that are:

  • Fully serviced and tested by our technicians
  • Backed by warranty for peace of mind
  • More affordable than new units — without sacrificing reliability
  • Available in multiple models and sizes to fit the needs of dermatology, dental, histology, and medspa practices

Choosing a refurbished autoclave from Amtech Medical gives you the confidence of a fully inspected and serviced machine at a fraction of the cost of new. It’s the perfect option for practices that need dependable sterilization without stretching their budget.

👉 Explore our current inventory of used autoclaves on our website or reach out to our team for availability.


Professional Autoclave Service & Support

While some issues with tabletop autoclaves can be fixed in-house, others require a trained technician. Electrical failures, sensor replacements, valve timing issues, and control board repairs should always be handled by professionals to avoid bigger (and more expensive) problems down the line.

At Amtech Medical, we provide:

  • Nationwide Service Coverage – Our technicians travel to support practices across the U.S.
  • Preventive Maintenance Programs – Keep your autoclave reliable with scheduled inspections and cleanings.
  • Emergency Repairs – Fast turnaround when your sterilizer goes down unexpectedly.
  • Multi-Device Support – We service autoclaves alongside your other dermatology, lab, and general medical equipment.

Our goal is simple: minimize downtime and keep your practice running smoothly. With decades of experience across autoclaves, lasers, and diagnostic equipment, our team has the expertise to troubleshoot quickly and get your sterilizer back in operation.

👉 Contact us today to schedule preventive maintenance or request an urgent repair.


The Most Common Problems with Leica Cryostats (And How to Fix Them)

Leica medical imaging equipment with advanced diagnostic capabilities.

Leica Biosystems is a German manufacturer known for histology and laboratory equipment, microscopes, and cameras. But among all their products, Leica cryostats stand out as the industry gold standard. They’re durable, user-friendly, and reliable — often praised by both technicians and repair engineers. Still, even the best equipment has its quirks, and Leica cryostats are no exception.

Below, we’ll cover the most common Leica cryostat problems, explain their likely causes, and walk through practical fixes.


Inconsistent Cutting (Thick and Thin Sections)

Symptoms: Tissue sections come out uneven, with ridges that alternate between thick and thin. This makes diagnosis more difficult and wastes sample material.

Likely Causes:

  • Loose locking levers on the blade holder
  • Blade holder not tightly secured to the microtome base
  • Misaligned front and rear pressure plates
  • Worn or warped tensioning springs
  • Blade angle improperly adjusted

Fix:
Start with the blade holder system before assuming deeper mechanical failure:

  1. Check all levers — confirm every locking lever is fully tightened. Even a small amount of play can cause inconsistent sectioning.
  2. Inspect blade holder mounting — ensure the blade holder is seated firmly on the microtome base.
  3. Check pressure plates — the front and rear plates must be aligned evenly. A warped plate creates uneven tension against the blade.
  4. Examine springs — if the rear tension springs are worn, replace them. Over time, weakened springs reduce stability and cause chatter.
  5. Reset blade angle — Leica recommends adjusting the angle gradually (typically between 5–10°) until sections cut smoothly.

👉 If problems persist after these checks, the issue may be with the internal microtome mechanics (cam, bearings, or advance system). At that point, call for service.


Cryostat Defrosting in the Middle of the Day

Cause: The automatic defrost cycle is scheduled at the wrong time.

Fix:

  1. Verify the set time — make sure the cryostat’s internal clock reflects the current time (e.g., 2:00 p.m. should display 14:00 if using 24-hour time).
  2. Check defrost timer — schedule defrost for off-hours (midnight–1:00 a.m. works well in most labs). Defrost cycles usually last 60–90 minutes, during which the cryostat is unusable.
  3. Adjust based on workflow — if the lab runs late, move defrost later (e.g., 3:00 a.m.).

👉 If defrost is still occurring during active hours even after adjusting, the defrost valve may be stuck or malfunctioning. A technician can test the valve and replace it if necessary.


Object Head Not Advancing

Symptoms: The object head won’t move forward or backward with the buttons, or the automatic advance feature doesn’t work with the handwheel.

Possible Causes & Fixes:

  • Electronic issue: If the buttons don’t respond at all, the problem could be a failed motor or faulty wiring. In this case, service is required.
  • Ice buildup: If the motor hums but the head doesn’t move, ice may be locking the micrometer system. Try:
    1. Defrost fully — power off the cryostat, open the chamber window, and leave it at room temperature for 24–48 hours until all condensation evaporates. Restart only when fully dry.
    2. Rapid method — set micrometer advance to maximum (50–60 microns per turn) and rotate the handwheel. This may break through light ice buildup.

👉 If the head remains stuck after full defrosting, the micrometer drive may be damaged and professional service is required.


Specimen Splintering (Too Cold)

Cause: Chamber temperature set below Leica’s recommended operating range (e.g., –27°C). While this speeds freezing, it makes specimens brittle and prone to splintering.

Fix:

  1. Warm the specimen slightly — pressing your thumb briefly on the sample adds enough heat to allow a smoother cut.
  2. Adjust temperature — Leica recommends –23°C for Mohs surgery. Small adjustments can dramatically improve section quality.
  3. Avoid overcooling for speed — many labs drop to –27°C for faster freezing, but this sacrifices cut quality. Prioritize proper temperature over throughput.

Specimen Mushing (Too Warm)

Cause: The specimen hasn’t cooled long enough or the cryostat chamber isn’t reaching target temperature.

Fix:

  1. Use the heat extractor block — keep it on the specimen for 10 minutes before sectioning. This ensures uniform freezing.
  2. Verify chamber temperature — the display should read below –21°C. If it remains warmer, allow extra time to cool.
  3. Check cooling performance — if the cryostat can’t maintain set temperature, there may be an issue with the refrigeration system. Call for service if necessary.

Cryostat Not Cooling Down

Symptoms: The chamber remains warm, and the compressor doesn’t engage.

Possible Causes & Fixes:

  • Error codes: Messages like E02, E20, E21, or E22 may indicate moisture or chamber issues.
    • Fix: Acknowledge the error by pressing any button. This often restarts the compressor.
  • Mechanical failure: If the compressor won’t run after clearing errors, possible causes include:
    • Failed compressor motor
    • Faulty fan motor or evaporator
    • Refrigerant leak

👉 If these components are at fault, only a trained service technician can repair them.


Final Thoughts

Leica cryostats are unmatched in quality and reliability, but even the best machines require maintenance. By understanding the most common issues — from thick-and-thin cutting to cooling failures — histology and Mohs technicians can troubleshoot faster, avoid wasted specimens, and reduce downtime.

When issues can’t be solved by checking blade holders, timers, or simple defrosts, don’t hesitate to call in professional service. With proper use and maintenance, a Leica cryostat will provide years of precise, dependable performance.


Amtech For Service

Do you need help with your equipment? Amtech Medical is here to help

Contact page for service


The Most Common Problems with Midmark Chairs (And How to Fix Them)

Adjustable medical examination chair for healthcare diagnostics and patient comfort.

Midmark exam chairs are some of the most trusted and widely used pieces of equipment in medical and dermatology practices. Known for their heavy base plate (weighing around 400 pounds), these chairs maintain a low center of gravity, offering unmatched stability even with heavier patients raised high in the air. Compared to lighter alternatives like Silverfox chairs, which lack a stabilizing base and can feel top-heavy, Midmark chairs are safer, sturdier, and built with high-quality American-made motors and components.

They don’t use real leather — instead, Midmark opts for synthetic fabrics and plastics in non-structural areas, while relying on durable metals and actuators that are designed to outlast most competitors. Still, no piece of equipment is immune to wear and tear. Below are the most common Midmark chair problems users encounter, what causes them, and how to fix or prevent them.


Hand Controller Cable Damage

One of the most frequent (and preventable) issues involves the hand controller. Many users hang the controller over the armrest mounting rail, letting it dangle. Over time, the constant tension frays the coiled black cord, eventually exposing internal wires. Once this happens, the controller stops working and the only fix is a replacement cable — a $350 part.

Signs to watch for:

  • Cracks or breaks in the black coiled cord
  • Exposed wires underneath the plastic insulation
  • Intermittent or no response from the controller

Solution: Avoid hanging the controller on the armrest. Instead, use inexpensive mounting buttons or holsters (around $7 each) that attach to the armrest rails. These keep the controller secure and dramatically reduce wear on the cord.

ED treatment table with medical ergonomic design for healthcare facilities.

Midmark Mounting Button

Product Page

Footrest Not Moving Up or Down

If the footrest isn’t responding, it’s often not an electrical issue at all but rather a safety lockout built into the chair’s design.

Common causes:

  • The storage drawer located beneath the seat isn’t fully pushed in. If extended, it blocks footrest movement to prevent a collision.
  • The footrest extension is partially pulled out. Unless fully retracted, the chair won’t allow movement.

Fix:

  • Push the under-seat drawer fully in until it clicks.
  • Retract the footrest extension completely.
  • If the problem persists, unplug and replug both the chair and the controller to reset connections.

These are simple user checks that can save a service call.


Chair Completely Unresponsive (No Movement at All)

Sometimes a Midmark chair will stop responding entirely after a power surge or fluctuation. This happens when the control board’s memory is disrupted.

First steps to try:

  • Unplug and replug the chair.
  • Disconnect and reconnect the controller.

If that doesn’t work, the issue may require a memory reset procedure on the main board. Important note: this must be performed by a certified technician. Attempting to reset the board incorrectly can further corrupt the memory and even damage the circuitry, requiring a full board replacement.

Other possible causes include blown fuses or a failed control board, but these are usually diagnosed after the simpler checks.


Controller Ports and Connector Damage

Another frequent issue comes when multiple controllers (hand and foot) are plugged in. Sometimes the hand controller stops working while the foot control still functions.

The culprit is often the connector at the back of the chair. Staff walking around the chair may accidentally kick the plug, bending or damaging the small pins inside. Once bent, the controller will no longer communicate with the chair.

How to fix:

  • Disconnect the controller and inspect both sides of the connector. Look for bent or broken pins.
  • Check the socket on the chair itself for damage.
  • If damaged, send the controller in for service or replacement.

Prevention: Install a protective security bracket around the connector. These brackets act like guards, preventing accidental kicks from damaging the port.


Actuator Motor Wear

Though Midmark uses durable American-made actuator motors, they can wear out over years of use. Signs include jerky chair movement, failure to fully raise or lower, or strange noises when adjusting positions.

Solution: Worn actuators require replacement. While less common than cable or connector issues, actuator failure is still a predictable maintenance concern after long-term use.


Best Practices to Prevent Midmark Chair Problems

  • Always use holsters or mounting buttons for hand controllers.
  • Keep the under-seat drawer and footrest extension fully retracted before adjusting chair positions.
  • Protect connectors with security brackets to prevent accidental kicks.
  • Unplug and replug after power fluctuations before calling for service.
  • Schedule preventive maintenance yearly to inspect actuators, fuses, and wiring.

Final Thoughts

Midmark chairs stand apart from cheaper alternatives thanks to their heavy base plate, stability, and reliable American-made motors. However, even the best chairs require proper handling and maintenance. Most problems — from damaged cords to blocked footrests — come down to user habits and can be avoided with simple best practices.

By addressing small issues early and taking preventive steps, you can dramatically extend the life of your Midmark exam chair while reducing costly repairs and downtime.

/product

The Most Common Problems with the Cutera Enlighten (and How to Fix Them)

High-tech laser medical device for dermatology and aesthetic treatments.

Introduction

The Cutera Enlighten is a premium dual-pulse laser system used for tattoo removal and advanced skin treatments. Known for its picosecond and nanosecond pulse technology, it delivers faster results and less tissue damage than older lasers.

But like all advanced medical devices, it can experience issues over time. In this guide, we’ll break down the most common Cutera Enlighten problems, their causes, and how to fix them—so you can minimize downtime and keep treatments running smoothly.


Loss of Tissue Effectiveness (Dirty or Damaged Lens Insert)

Symptoms:
Treatments seem less effective even though no error codes are present.
Patients notice slower results.

Cause:
Debris such as skin particles, hair, and treatment residue accumulates on the lens insert inside the handpiece. Over time, the laser beam can burn small spots into the lens coating, reducing power and focus.

Solution:
Inspect the lens insert regularly for buildup or burn marks.
Replace the lens insert when performance drops. Cutera ships them pre-mounted for quick swaps.
Clean the lens daily with a Q-tip dipped in acetone or 91%+ isopropyl alcohol. This can extend lens life from about 1 year to up to 2 years depending on usage.

Why it matters:
A clean, undamaged lens ensures maximum energy delivery, shorter treatment times, and happier clients.


Cutera Enlighten Error Code 1530 – Energy Detector Mismatch

Symptoms:
The machine stops firing and displays Error 1530.

Cause:
The Enlighten has two internal energy detectors—one “main” and one “safety.” If they disagree on energy output by more than 20%, the system triggers this error to prevent unsafe operation.

Solution:
This is not user-fixable and requires calibration by a certified laser technician.
It is often resolved during annual preventive maintenance visits, where detectors are tested and recalibrated.
If the error appears between PMs, call for service immediately.

More information from medwrench form can be found here


Cutera Enlighten Error Code 1125 – Delay Line Failure

Symptoms:
The laser will not fire in any wavelength or mode.
Error 1125 appears on the screen.

Cause:
A failure in the delay line, which is a series of optics that switch between picosecond and nanosecond pulses. The most common culprit is the LCR (Liquid Crystal Retarder), which controls light polarity.

Solution:
This is a hard failure requiring professional repair.
The LCR often needs replacement and alignment, which can only be done by a certified Cutera technician.


Keeping the Cutera Enlighten Reliable

The Cutera Enlighten has an excellent track record for results—especially in tattoo removal—but regular care is essential.

Best practices for owners:
Daily lens cleaning to prevent debris buildup.
Annual preventive maintenance visits for calibration and internal cleaning.
Prompt service calls for any error codes.

With consistent maintenance, most clinics report that the Enlighten runs reliably and delivers consistently excellent results.


Final Thoughts

The most common Cutera Enlighten problems—lens contamination, error 1530, and error 1125—are well-understood, preventable in some cases, and easily resolved with proper maintenance.

If you own or operate an Enlighten, building these preventive steps into your workflow will help ensure maximum uptime and client satisfaction.


The Most Common Problems with the Candela Gentle Max (and How to Fix Them)

Medical laser treatment device with handheld applicator and adjustable arm, used for cosmetic and dermatological procedures.

What Is the GentleMax Pro?

The Candela GentleMax Pro is a highly celebrated, dual-wavelength laser platform renowned in the aesthetics and dermatology community. Here’s what makes it stand out:

  • Dual-wavelength system: It houses both a 755 nm Alexandrite laser (ideal for lighter skin tones and fine to medium hair) and a 1064 nm Nd:YAG laser (safer for darker skin tones and coarse hair) — enabling treatment across all Fitzpatrick skin types.
  • Versatile treatment capabilities: Beyond hair removal, it’s effective for pigmented lesions, vascular concerns, skin tightening, wrinkle reduction, and more.
  • Advanced cooling and efficiency: Equipped with Candela’s Dynamic Cooling Device (DCD), it delivers precise chilling bursts to protect the epidermis and enhance patient comfort. Large spot sizes (up to 24 mm) and high repetition rates allow for fast, efficient sessions.
  • Proven track record: A trusted system with over two decades of clinical use, installed globally in dermatology practices, medspas, and hospitals. Clinicians praise its reliability, performance, and patient

Error 15.1 – Delivery System Transmission Low

When energy loss exceeds 20% between the laser and handpiece, the system triggers this error. Typical causes include:

  • ⚠️ Cause: Damaged debris shield — Replace the protective shield, recalibrate, and retest.
  • ⚠️ Cause: Fiber-end damage or breakage — Often due to wear, mishandling, or accidental impact. Replace the fiber if required.
  • ⚠️ Cause: Internal lens damage — May follow fiber issues; requires professional repair.

This error is one of the most common and can significantly affect treatment effectiveness if left unresolved. The debris shield plays a crucial role in protecting delicate optics from contamination, so regular inspection and replacement are vital. Fiber damage often results from everyday use or accidental impacts, emphasizing the importance of careful handling and proper storage. Addressing these issues promptly helps maintain consistent laser energy delivery and prevents costly repairs down the line.


Error 26.1 / 26.2 – Internal Fiber Software Fault

These indicate communication glitches or memory faults within the system.

Quick fix: Power off, unplug for one minute to discharge capacitors fully, then reboot. Persistent errors may require software reload.

These internal fiber software faults can disrupt treatment flow and cause unexpected downtime if not addressed promptly. Often, a simple power cycle resets the system’s electronics and clears temporary glitches. However, if errors persist, it may indicate deeper software corruption or hardware issues requiring a technician to reload or update the system software. Regular software maintenance and updates help minimize these faults and keep your GentleMax Pro operating smoothly.


Error 12.1 – Low Energy Output

This signals problems within the laser’s pump chamber, which houses lamps, rod, and reflector:

  • ⚠️ Cause: Worn flashlamps — Replaceable and less costly; often a quick fix
  • ⚠️ Cause: Damaged rod or pump chamber — May necessitate full assembly replacement (lamps, rod, chamber).

Low energy output can significantly impact treatment results, leading to longer session times and reduced effectiveness for patients. In most cases, the issue stems from wear and tear within the pump chamber components, which naturally degrade over time due to repeated high-energy pulses. Regular maintenance and timely replacement of worn flashlamps can prevent more serious damage to the rod or reflector, ultimately extending the lifespan of the GentleMax Pro and ensuring consistent performance.


Summary

The Candela GentleMax Pro is a powerful, versatile laser system widely respected for its effectiveness across all skin types. However, like any precision medical device, it requires regular maintenance and careful handling to perform optimally. Common issues such as fiber transmission errors, internal software faults, and low energy output often arise from wear and tear or miscommunication within the system.

Timely identification and resolution of these problems are crucial to minimizing downtime and ensuring patient safety and satisfaction. Simple preventative measures—such as routinely inspecting and replacing debris shields and fibers, performing system resets when needed, and scheduling professional maintenance for the pump chamber—can extend the lifespan of your device and keep treatments efficient.

Ultimately, proactive care not only safeguards your investment but also helps maintain consistent treatment quality, supporting your clinic’s reputation and patient trust.


The Most Common Problems with Sakura Tissue Processors (and How to Fix Them)

High-precision medical diagnostic device with touchscreen interface and storage drawers.

What Is a Tissue Processor?

A tissue processor is a vital instrument in histology labs, used to prepare tissue samples for microscopic examination. When tissue is removed from the body—whether through biopsy or surgery—it needs to be preserved and processed before it can be sliced, stained, and reviewed by a pathologist.

Tissue processors like those from Sakura automate this process. They move tissue samples through a series of chemical stations that remove water, replace it with alcohol, and eventually embed the tissue in paraffin wax. This automation ensures consistency, accuracy, and efficiency across large volumes of samples.


The Most Common Problems We See with Sakura Tissue Processors

At Amtech, we frequently work with labs using Sakura processors, and we often see a few recurring problems. Below are two of the most common issues—and how to troubleshoot them. A list of the tissue Tek Line up can be found below.

ModelKey Feature
VIP 1000 / 2000 / 3000Classic benchtop/floor models with varied capacity
VIP 5Flexible software, continuous mixing, easy control
VIP 6Enhanced reagent automation & interface
VIP 6 AIAutomatic mixing, remote support, advanced control
Xpress x120Rapid, continuous microwave‑vacuum processing

Problem #1: Station 3 Fails to Pump In or Out

A frequent user-repairable issue is a failure to pump in or pump out on station 3.

Here’s why it happens: Sakura tissue processors are usually set up with 10% neutral buffered formalin in stations 1 and 2, while station 3 holds alcohol. When formalin and alcohol interact, they produce sodium. Over time, sodium crystallizes and begins to clog the lines and connectors, especially in station 3.

How to Fix It:

The best solution is a hot water flush, which should be part of routine maintenance.

Here’s how to perform the flush:

  1. Fill the few water bottle with very hot (not boiling) water.
  2. Place the water into station 1 and manually pump in and pump out.
  3. Repeat for station 2.
  4. For station 3, use fresh hot water and pump in and out 2–3 times.
  5. Optionally flush station 4 to remove remaining sodium from the system.
  6. Return the water bottle to its standard position and test station 3 again.

If station 3 now pumps freely, the issue is resolved. Sakura recommends performing this flush every 4–5 processing cycles to prevent build-up.


Problem #2: Vacuum or Pressure Failure

Another common issue is a vacuum or pressure failure. This may require formal repair service, but there’s one thing you can check yourself: the retort lid gasket.

If this gasket isn’t sealing properly, the system can’t build or maintain vacuum and pressure.

How to Check It:

  1. Start a pump cycle on any station.
  2. While it’s running, listen around the retort lid.
  3. If you hear hissing sounds, the lid gasket is likely leaking.

In that case, contact Amtech. We can ship you a replacement gasket and walk you through the easy installation process.


Prevent Problems with Routine Maintenance

The key to preventing both of these issues is consistent maintenance. A hot water flush every few cycles can dramatically extend the life of your processor and prevent clogs. Listening for vacuum leaks during pump cycles can help catch gasket issues early.

If you’re experiencing problems with your Sakura processor or just want help with preventive maintenance, Amtech is here to support your lab every step of the way.